A request for a “HEPA box” can mean several different purchases: an empty welded shell, a housing with its filter-retaining hardware, or a complete powered filtration assembly. Those quotations cannot be compared until the buyer identifies what is included. For an equipment OEM, the useful starting point is a bill of materials tied to an assembly drawing.
A metalwork supplier needs the filter envelope and service requirements even when another company supplies the filter. Equally, a housing drawing should not quietly make the fabricator responsible for fan selection, controls or the completed equipment’s filtration performance. Agreeing those interfaces early prevents missing hardware from appearing as a late assembly problem.
Separate the supplied assembly into functional packages
List the shell, mounting flanges, filter seat, door, clamps, bought-in seals and test-port fittings separately. State which items are supplied loose and which arrive assembled. A door handle in a rendering is not a purchased component unless it appears in the released scope.
A fan-filter unit adds a fan and its associated electrical and airflow interfaces. If your order covers only the metalwork, provide the fan mounting envelope without describing the delivered shell as a complete FFU. Identify the party that selects the filter, approves seal compatibility and performs system commissioning.

Build the RFQ around the selected filter interface
Use the selected filter’s current dimensional information, not only its nominal width and height. The sealing arrangement, frame depth, retaining edge and installation direction affect the surrounding fabrication. A gel-seal seat and a compressed-gasket flange need different interface details; neither can be reconstructed reliably from an external enclosure size.
Provide the seat datum, the permitted distortion after welding and the finished condition in which measurements are taken. If a machined insert establishes the reference surface, identify its material and fastening arrangement. Keep the drawing revision for that insert linked to the shell revision.
| Package | Information to release | Acceptance owner |
|---|---|---|
| Metal shell | Material, envelope, welds, flanges and finish | Fabricator against drawing |
| Filter and seal | Selected part, sealing geometry and compatibility | Equipment owner / filter supplier |
| Door and retention | Clamps, stops, access and adjusted condition | Agreed assembly scope |
| Fan and controls | Mounts, wiring boundary and operating requirements | System integrator |
| Testing | Method, ports, limits and sampled assembly | Named test or commissioning team |
Assign acceptance tasks before comparing prices
Dimensional inspection of a seal seat, a door fit check, housing-joint leakage and installed-filter integrity are different tasks. Describe each required task by its assembly state, method owner, sample quantity and acceptance reference. A supplier’s visual check of a weld does not replace an agreed leak test.
Testing access also belongs in the RFQ. The team carrying out the selected method should approve port locations and access requirements before cutting the shell. Camfil’s CleanSeal installation manual provides a useful manufacturer example of separately identified pressure, scan and sampling connections; it is not a specification for every housing.

Price the repeatable delivery condition
Ask for a quotation against a defined material grade, sheet thickness, surface treatment and delivery configuration. Separate prototype tooling or inspection fixtures from repeat-batch pricing. State whether clamp adjustment, seal installation, filter trial fitting or protective closure of ports is included.
Packaging should protect the surfaces that determine assembly, especially the seal seat and flange corners. Supply the required identification and cleaning condition, without inserting unsupported cleanroom classifications into the purchase description. A clear first-article package lets purchasing compare manufacturing scope instead of comparing a bare shell with an assembled housing.
Close the scope with an interface review
Before release, walk through how the filter enters, seats, clamps and exits. Check whether the door, nearby ductwork or test fittings obstruct any movement. Resolve missing information in the RFQ rather than allowing a shop-floor substitute to redefine the assembly.
In the linked customer project, the machining, clamping and customer filter trial were reported as separate pieces of evidence. Use that distinction when requesting a similar build: the results describe that project, while your design needs its own drawing and acceptance plan.

DRAmetal manufactures custom HEPA filter housings around released OEM interfaces. The filter-seat customer project provides a scoped example of dimensional inspection and customer trial assembly. Include your selected filter, mating details, quantities and required records when requesting a fabrication review.
Need a Custom Sheet Metal Quote?
Send us your CAD drawings — DRAmetal's initial response target is within 24 working hours. Quotation, DFM and lead-time timing depend on file completeness and engineering scope.
GET A FREE QUOTE →