A brush panel has two interfaces: the metal frame attaches to the rack, and the brush opening accommodates the harness. Checking only the first can leave a neat-looking panel that is difficult to cable. Checking only the second can produce a frame that fouls the rack or adjacent equipment.
For OEM rack kits, describe the installed harness state and the change operations the panel must support. The goal is a controlled metalwork interface, not an unsupported promise that a brush opening prevents every air leak.
Describe the occupied opening
Provide the expected bundle envelope, connector sizes and entry direction. A cable’s outer diameter does not capture the larger connector that must pass through during installation. Where terminated harnesses are used, include their maximum passing envelope and whether the brush or frame can be removed.
Identify spare capacity as a design input, not a vague request for flexibility. An opening sized for an undefined future bundle can become unnecessarily large or interfere with mounting lands. Document what is known and which additions require another interface review.

Keep the brush insert and metal frame distinct
Obtain the selected brush strip or cassette dimensions and its retention method. The frame must support the insert without crushing its mounting edge or leaving unsupported sections. Show replaceable components and the access needed to remove them.
If the insert is customer-supplied, establish who fits it and who checks the completed assembly. A metalwork quotation should not imply that a brush kit is included merely because the illustration shows bristles. Add the exact insert or an agreed approved-equivalent process to the bill of materials.
| Input | Why it matters | Acceptance focus |
|---|---|---|
| Harness envelope | Includes connectors and cable route | Installed and passing clearance |
| Brush insert | Defines frame retention | Seat and replaceable fixing |
| Rear space | Contains bends, nuts and flanges | No local interference |
| Service sequence | Determines removal requirements | Access with nearby equipment |
| System requirement | Defines any airflow objective | Separate agreed verification |
Review gaps in the actual installed state
Inspect the opening with the intended harness occupancy. A largely empty brush panel behaves differently from one crowded with several bundles. Cable direction, movement and bends can separate the bristles or hold the harness against a sharp frame edge.
Describe the physical interfaces the fabricator can control: cutout size, frame edges, insert retention and mounting position. Any quantified airflow or system thermal result needs its own test scope. Neither a close-up photograph nor the presence of a brush strip establishes a measured bypass rate.

Protect installation and maintenance access
Show the harness path on both sides of the rack face. Check that cable bends do not occupy the same space as a rear return flange or cage nut. Leave access for the installer to reach the panel fasteners without pulling on cables.
Consider the order of installation. If the panel must be removed to add a preterminated harness, demonstrate how that is done with neighboring equipment present. A service operation that requires unplanned disconnection of unrelated cables should be identified before the rack kit is released.
Inspect the delivered metalwork against the interface
Verify the opening, finished edge condition, mounting locations and brush retention features. Trial fit the selected insert and a representative harness where that is in the agreed scope. Record which components were present instead of describing a bare-frame check as a completed rack installation.
For a mixed rack order, keep brush panels distinguishable from solid blanks and vented panels. The occupancy schedule should state which function belongs at each opening. The same external height does not make these variants interchangeable during kitting or field replacement.