A wireway joint needs more than matching bolt holes. The adjacent bodies must establish the intended route, the internal transition must preserve the released cable envelope, and the covers must remain removable. A splice plate that can be bolted on is not proof that all three conditions have been met.
For custom sheet-metal wireways, treat each joint as an interface between two identified assemblies. Start with a connection schedule, then define locating features, finished hole patterns and the acceptance condition. This is particularly valuable where straight runs connect to elbows, offsets or cabinet adapters that can be installed in more than one orientation.
Establish which feature locates the route
Choose a reference that corresponds to the equipment installation: a mounting face, the wireway base plane, a controlled sidewall or a defined centerline. Explain how each section’s connection coordinates relate to that reference. Dimensions taken from an arbitrary cut edge may not reproduce the installed position when bend variation or end trimming changes the edge.
A connection drawing should also distinguish locating features from clamping features. A clearance hole permits assembly but does not necessarily locate the joint precisely. Slots may permit adjustment, but only within an approved direction and range. Do not enlarge or slot holes simply to hide an unresolved mismatch between two released parts.
The drawing should show the intended assembled gap or contact condition at the body ends. If the fit is evaluated using a fixture, identify which surfaces the fixture supports and which remain free. Otherwise, two inspectors can restrain the same thin-walled part differently and obtain incompatible results.

Release the hole pattern as a shared interface
Create one controlled interface definition used by the straight section, elbow and joiner drawings. Include its revision in the relevant parts list. This is more reliable than independently redrawing a nominally identical hole pattern on several components and hoping that later changes remain synchronized.
Dimension the pattern in the formed condition. A flat blank’s hole position does not fully describe where that hole ends up relative to the installed trough base after bending. Where the pattern sits near a bend, review the available flat fastening area and the installed washer or head rather than checking hole centers alone.
Specify the hardware stack and assembly direction. An internal nut, a retained nut and an externally installed fastener create different access and intrusion conditions. Decide which arrangement suits the approved routing space before the fabrication supplier chooses tooling or hardware.
Give elbows a direction and a connection identity
“One elbow” is incomplete when a route includes top-opening sections, vertical changes or handed connections. Label each connecting face and show the fitting in its installed orientation. The cover opening direction and the side carrying a divider or support attachment should remain clear after the part has been removed from its shipping carton.
Manufacturer systems demonstrate how specific joint details can become. Hammond’s 1485 wireway documentation distinguishes flat and angle sealing plates at different junctions. That is a useful reminder to define each custom interface explicitly, not evidence that the same accessory or sealing result applies to another design.

Use a connection schedule to prevent mismatched kits
The schedule can be a short table attached to the assembly drawing. It should tell purchasing and inspection which components are supposed to meet and what must be checked at that junction.
| Schedule field | What to record | Why it matters |
|---|---|---|
| Joint identity | Route location and the two mating part revisions | Prevents mixing geometrically similar variants |
| Locating reference | Base plane, side datum and end condition | Makes assembly measurements repeatable |
| Connection hardware | Plate, approved fasteners and installation direction | Defines access and internal protrusion |
| Cover interface | Overlap, removal sequence and nearby obstructions | Preserves maintenance access at the junction |
| Electrical interface | Customer-approved bonding detail and required check | Keeps electrical continuity separate from visual fit |
| Acceptance state | Finish, supports, fixture and sample coverage | Avoids comparing bare loose parts with a finished route |
Inspect the inside of the assembled transition
Check the joint from the cable side as well as the outside. A plate can look flush externally while a screw end, nut or mismatched base edge occupies the intended routing envelope. The drawing should identify any permitted intrusion and required edge treatment, including interfaces that are difficult to see after assembly.
The OEM supplies the cable or harness constraints, including its approved bend and installation envelope. The fabricator can then inspect whether the metal assembly conforms to those dimensions. Do not substitute a generic bend clearance or claim electrical suitability from a smooth-looking joint alone.
Cover access deserves its own check. If a plate overlaps the lid, or if adjoining covers require an impossible removal sequence, hole alignment will not resolve the problem. Use the cover-fit checklist during the same trial assembly.

Check the route without forcing it into alignment
Trial-assemble a meaningful combination of straight sections and fittings using the specified supports or inspection fixture. Check the overall route coordinates as well as individual joints. Small permitted deviations can accumulate, especially where the final section must connect to a fixed cabinet opening.
Record whether the parts seat naturally or require pulling into position with the fasteners. An assembly that depends on unapproved distortion may lose cover fit or load the adjoining equipment. Disposition the cause through the drawing or process review rather than normalize force-fitting as an assembly instruction.
Finally, keep the inspection record tied to actual part revisions, finish condition and sample coverage. The metal wireway customer project connects these joint decisions with cover and entry planning. Together with the OEM supply-scope checklist, it provides a practical route from approved interfaces to repeatable metalwork kits.